Parameterization¶
Firmware version | Configuration |
---|---|
Firmware version > V2.0.0 | The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software. |
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module: Module slot address: Y = 1…10
Name | Value | Internal value | Internal value, type | Default | EDS Slot / Index |
---|---|---|---|---|---|
Module ID 1) |
Internal | 1810 | WORD | 1810 | 0x0Y01 |
Ignore module see table 2) |
Internal | Yes No |
BYTE | No | not for FBP |
Parameter length | Internal | 8 | BYTE | 8 | 0xY02 |
Check supply | off | 0 | BYTE | 1 | 0xY03 |
on | 1 | ||||
Fast counter 3) |
0 : 10 4) |
0 : 10 |
BYTE | 0 | not for FBP |
Behavior outputs at comm. error 5) |
Off Last value Last value 5 sec Last value 10 sec Substitute value Substitute value 5 sec Substitute value 10 sec |
0 1 6 11 2 7 12 |
BYTE | Off 0x00 |
0x0Y07 |
2) | Setting | Description |
---|---|---|
On | Error-LED lights up at errors of all error classes, Failsafe mode off | |
Off by E4 | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe mode off | |
Off by E3 | Error LED lights up at errors of error classes E1 and E2, Failsafe mode off | |
On +Failsafe | Error-LED lights up at errors of all error classes, Failsafe mode on* | |
Off by E4 + Failsafe | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe mode on* | |
Off by E3 + Failsafe | Error LED lights up at errors of error classes E1 and E2, Failsafe mode on* |
Remarks:
1) With a faulty ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission
2) Not for FBP
3) With FBP or CS31 without the parameter “Fast Counter”
Note
The fast counter of the module does not work if the module is connected to an FBP interface module or CS31 bus module.
4) For counter operating modes, please refer to the description of the fast counter Fast Counter
5) The parameter Behavior outputs at comm. error is only analyzed if the Failsafe-mode is ON.