Channel \ parameters for the analog outputs (2x)

Name Value Internal value Internal value, type Default EDS Slot / Index

0

Output 0, Channel configuration

see DA501 - Digital/Analog Input/Output Module see DA501 - Digital/Analog Input/Output Module BYTE 0 0x0Y11
Output 0, Check channel see DA501 - Digital/Analog Input/Output Module see DA501 - Digital/Analog Input/Output Module BYTE 0 0x0Y12
Output 0, Substitute value see DA501 - Digital/Analog Input/Output Module see DA501 - Digital/Analog Input/Output Module WORD 0 0x0Y13
Output 1, Channel configuration see DA501 - Digital/Analog Input/Output Module see DA501 - Digital/Analog Input/Output Module BYTE 0 0x0Y14
Output 1, Check channel see DA501 - Digital/Analog Input/Output Module see DA501 - Digital/Analog Input/Output Module BYTE 0 0x0Y15
Output 1, Substitute value see DA501 - Digital/Analog Input/Output Module see DA501 - Digital/Analog Input/Output Module WORD 0 0x0Y16
Channel configuration
Internal value Operating modes of the analog outputs, individually configurable
0 (default) Not used
128 -10 V…+10 V
129 0…20 mA
130 4…20 mA
Channel monitoring
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Substitute value
Intended behavior of output channel  when the control system stops Required setting of the module parameter “Behavior of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then turn off Last value 5 sec 0
Last value for 10 s and then turn off Last value 10 sec 0
Substitute value infinite Substitute value Depending on configuration
Substitute value for 5 s and then turn off Substitute value 5 sec Depending on configuration
Substitute value for 10 s and then turn off Substitute value 10 sec Depending on configuration