Connection of active-type analog sensors (voltage) to differential \ analog inputs

Differential inputs are very useful if analog sensors which are remotely non-isolated (e.g. the negative terminal is remotely earthed) are used.

Using differential inputs helps to considerably increase the measuring accuracy and to avoid earthing loops.

With differential input configurations, two adjacent analog channels belong together (e.g. the channels 0 and 1). In this case, both channels are configured according to the desired operating mode. The lower address must be the even address (channel 0), the next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1).

The analog value is calculated by subtraction of the input value with the higher address from the input value of the lower address.

The converted analog value is available at the odd channel (higher address).

Caution

:strong:Risk of faulty measurements!

The negative pole at the sensors must not have too large a potential difference with respect to ZP (max. ± 1 V within the full signal range).

Make sure that the potential difference never exceeds ± 1 V.

The following figure shows the connection of active-type analog sensors (voltage) to differential analog inputs AI0 and AI1. Proceed with AI2 and AI3 in the same way.

../_images/8ba0ad85936114ed0a33139001be49b6

Connection of active-type analog sensors (voltage) to differential analog inputs

The following measuring ranges can be configured DA501 - Digital/Analog Input/Output Module DA501 - Digital/Analog Input/Output Module:

Voltage 0…10 V with differential inputs, 2 channels used
Voltage -10 V…+10 V with differential inputs, 2 channels used

For a description of the function of the LEDs, please refer to the Diagnosis and displays / Displays chapter DA501 - Digital/Analog Input/Output Module.

To avoid error messages from unused analog input channels, configure them as “unused”.