Electrical Connection

The digital/analog input/output module DA501 can be connected to the following devices via the I/O bus connector:

  • FBP interface module DC505-FBP
  • CS31 bus modules, e. g. DC551-CS31, CI590 and CI592
  • AC500 CPUs (PM5xx)
  • other AC500-I/O devices.

Note

For a detailed description of the mounting, disassembly and electrical connection of the module, please refer to the System Assembly chapter AC500-eCo.

The electrical connection is carried out by using the 40 terminals of the terminal unit TU515/TU516 TU515, TU516, TU516-H and TU542 for I/O Modules.

The assignment of the terminals:

Terminal Signal Description
1.0 DI0 Signal of the digital input DI0
1.1 DI1 Signal of the digital input DI1
1.2 DI2 Signal of the digital input DI2
1.3 DI3 Signal of the digital input DI3
1.4 DI4 Signal of the digital input DI4
1.5 DI5 Signal of the digital input DI5
1.6 DI6 Signal of the digital input DI6
1.7 DI7 Signal of the digital input DI7
1.8 UP Process voltage UP (24 VDC)
1.9 ZP Process voltage ZP (0 VDC)
2.0 DI8 Signal of the digital input DI8
2.1 DI9 Signal of the digital input DI9
2.2 DI10 Signal of the digital input DI10
2.3 DI11 Signal of the digital input DI11
2.4 DI12 Signal of the digital input DI12
2.5 DI13 Signal of the digital input DI13
2.6 DI14 Signal of the digital input DI14
2.7 DI15 Signal of the digital input DI15
2.8 UP Process voltage UP (24 VDC)
2.9 ZP Process voltage ZP (0 VDC)
3.0 AI0+ Positive pole of analog input signal 0
3.1 AI1+ Positive pole of analog input signal 1
3.2 AI2+ Positive pole of analog input signal 2
3.3 AI3+ Positive pole of analog input signal 3
3.4 AI- Negative pole of analog input signals 0 to 3
3.5 AO0+ Positive pole of analog output signal 0
3.6 AO1+ Positive pole of analog output signal 1
3.7 AO- Negative pole of analog output signals 0 and 1
3.8 UP Process voltage UP (24 VDC)
3.9 ZP Process voltage ZP (0 VDC)
4.0 C16 Signal of the configurable digital input/output C16
4.1 C17 Signal of the configurable digital input/output C17
4.2 C18 Signal of the configurable digital input/output C18
4.3 C19 Signal of the configurable digital input/output C19
4.4 C20 Signal of the configurable digital input/output C20
4.5 C21 Signal of the configurable digital input/output C21
4.6 C22 Signal of the configurable digital input/output C22
4.7 C23 Signal of the configurable digital input/output C23
4.8 UP Process voltage UP (24 VDC)
4.9 ZP Process voltage ZP (0 VDC)

The internal power supply voltage for the module’s circuitry is carried out via the I/O bus (provided by a bus module or a CPU). Thus, the current consumption from 24 VDC power supply at the terminals L+/UP and M/ZP of the CPU/bus module increases by 2 mA per DA501.

The external power supply connection is carried out via the UP (+24 VDC) and the ZP (0 VDC) terminals.

Attention

:strong:Risk of damaging the PLC modules!

Overvoltages and short circuits might damage the PLC modules.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you begin with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.

Attention

:strong:Risk of damaging the PLC modules!

The PLC modules must not be removed while the plant is connected to a power supply.

Make sure that all voltage sources (supply and process voltage) are switched off before you

  • connect or disconnect any signal or terminal block
  • remove or replace a module.

Caution

:strong:Risk of imprecise and faulty measurements!

Analog signals may be distorted seriously by external electromagnetic influences.

Use shielded wires when wiring analog signal sources. The cable shield must be grounded at both ends of the cable. Provide a potential equalization of a low resistance to avoid high potential differences between different parts of the plant.

../_images/59a85bfd8fbe6bb20a3313904e3ae81c

Terminal assignment of the module

The module provides several diagnosis functions DA501 - Digital/Analog Input/Output Module.