Connection of active-type analog sensors (voltage) with no electrically \ isolated power supply to the analog inputs¶
The following figure shows the connection of active-type analog sensors (voltage) with no electrically isolated power supply to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Connection of active-type sensors (voltage) with no electrically isolated power supply to the analog inputs
Caution
:strong:Risk of faulty measurements!
The negative pole at the sensors must not have a too big potential difference with respect to ZP (max. ± 1 V within the full signal range).
Make sure that the potential difference never exceeds ± 1 V.
The following measuring ranges can be configured DA501 - Digital/Analog Input/Output Module DA501 - Digital/Analog Input/Output Module :
Voltage | 0…10 V | 1 channel used |
Voltage | -10 V…+10 V | 1 channel used |
For a description of the function of the LEDs, please refer to the Diagnosis and displays / Displays chapter DA501 - Digital/Analog Input/Output Module.
To avoid error messages from unused analog input channels, configure them as “unused”.