Connection of active-type analog sensors (voltage) with no electrically \ isolated power supply to the analog inputs

The following figure shows the connection of active-type analog sensors (voltage) with no electrically isolated power supply to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.

../_images/8aeaec7c935a98ff0a331390018307cf

Connection of active-type sensors (voltage) with no electrically isolated power supply to the analog inputs

Caution

:strong:Risk of faulty measurements!

The negative pole at the sensors must not have a too big potential difference with respect to ZP (max. ± 1 V within the full signal range).

Make sure that the potential difference never exceeds ± 1 V.

The following measuring ranges can be configured DA501 - Digital/Analog Input/Output Module DA501 - Digital/Analog Input/Output Module :

Voltage 0…10 V 1 channel used
Voltage -10 V…+10 V 1 channel used

For a description of the function of the LEDs, please refer to the Diagnosis and displays / Displays chapter DA501 - Digital/Analog Input/Output Module.

To avoid error messages from unused analog input channels, configure them as “unused”.