Technical Data of the Analog Inputs

Parameter Value
Number of channels per module 4 configurable thermocouple (TC) inputs
Distribution of channels into groups 1 (4 channels per group)
Resolution  
  Temperature 0.1 °C
  Voltage 15 bits plus sign
Connection of the signals I0+ to I3+ Terminals 1, 3, 5 and 7
Connection of the signals I0- to I3- Terminals 2, 4, 6 and 8
Input type Floating thermocouple
Galvanic isolation Against internal power supply and other modules
Common mode rejection > 120 dB at 120 V AC
Indication of the input signals No
Module update time All channels: < 1.6 s
Channel input resistance On request
Input filter attenuation -3 dB at 15 kHz
Cold junction error ± 1.5 °C
Basic error 0.1 % of full-scale (voltage)
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

Depending on thermocouple, see table below

at 25 °C

Max.

± 2 % of full scale (T-Type: ± 3 % for -240… -270 °C)

at 0 … 60 °C

Relationship between input signal and hex code Table AI563 - Analog Input Module
Analog to digital conversion time 400 ms per channel
Unused inputs Can be left open and should be configured as “unused”
Input data length 8 bytes
Overvoltage protection Yes, up to 30 V DC
Repeatability On request
Wire loop resistance < 100 W
Max. cable length (conductor cross section > 0,14 mm²)  
  Unshielded wire 10 m
  Shielded wire 100 m