Technical Data

The System Data of AC500-eCo apply System Data AC500-eCo

Only additional details are therefore documented below.

Parameter Value
Process supply voltage UP  
  Connections Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V)
  Rated value 24 V DC
  Current consumption 0.10 A
  Inrush current (at power-up) 0.07 A²s
  Max. ripple 5 %
  Protection against reversed voltage Yes
  Rated protection fuse for UP Not necessary
Current consumption from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/bus module Ca. 5 mA
Galvanic isolation Yes, between the channels and the rest of the module
  Isolated groups 1 (4 channels per group)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 2.6 W
Weight Ca. 120 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.