Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Parameter | Value |
---|---|
Protocol | PROFINET I/O RT |
Bus connection | 2 x RJ45 (PNIO1 and PNIO2), with integrated 2-port switch |
Switch | Integrated |
Technology | Hilscher netX100 |
Transfer rate | 100 MBit/s (full-duplex) |
Transfer method | According to ETHERNET II, IEE802.3 |
Bus length (segment length max.) | 100 m |
Indicators | 5 LEDs |
Usable terminal bases | All TB5xx TB51x-TB54x All TB56xx: TB56xx |
Supported alarm types | Process alarm, diagnostic alarm, return of SubModule, plug alarm, pull alarm |
Alarm processing | Requires handling in application program |
Current consumption from 24 V DC power supply at the terminal base of the CPU | Typ. 85 mA |
Internal supply | Via the communication module interface of the terminal base |
Weight | Ca. 170 g |
Supported protocols | RTC - real-time cyclic protocol, class 1 RTA - real-time acyclic protocol DCP - discovery and configuration protocol * CL-RPC - connectionless remote procedure call Since revision FW 2.4.8.0 additionally LLDP - link layer discovery protocol SNMP - simply network management protocol (SNMP v1) |
Acyclic services | PNIO read / write (max. 1392 bytes per telegram, max. 4096 bytes per service request) |
Total quantity of input and output data | CM579-PNIO < FW 2.4.8.0 1024 bytes input and output data per IO device but in total 3072 bytes input output data CM579-PNIO = FW 2.4.8.0 1024 bytes input and output data per IO device but in total 4096 bytes input output data CM579-PNIO > FW 2.4.8.0 1440 bytes input and output data per IO device but in total 4096 bytes input output data |
Min. bus cycle | 1 ms |
Conformance class | CC A |
* CM579-PNIO does not allow setting “Station name” by using PROFINET service “DCP SET NameOfStation”.