State LEDs

The PROFINET state is shown by the state LEDs.

../_images/b0e29c83d64cd9bb0a317f345fd1e2c2

Position of the LEDs

Meaning of the diagnosis LEDs:
LED Color State Description
PWR Green On Power supply available
Blinking
Off Power supply not available or defective hardware
RDY Yellow On Boot procedure
Blinking Boot failure
Off
RUN Green On Communication module is operational
Blinking
Off Communication module is not operational
STA1 PNIO Red On In incorporation with STA2 PNIO: License fault
Blinking System error
Off No system error
STA2 PNIO Red On No connection; in incorporation with STA1 PNIO: license fault
Blinking Configuration fault: some configured IO Devices are not connected
Off No bus error, communication is running
STA1 and STA2

Red

Green

Blinking (synchronously) Firmware file transfers during coupler firmware update

Red

Green

Blinking (alternately) Coupler writes the firmware file to the internal flash. Do not power off the PLC.

Yellow

Yellow

Blinking (synchronously) No production data available, no bus communication possible.

The RJ45 ETHERNET connector contains two LEDs showing the current ETHERNET port connection state. The following figure and table show the position and function of the LEDs:

../_images/9a83d05fe387c3a30a33139000eba54e

Position of the LEDs in the RJ45 connectors

Meaning of the diagnosis LEDs:
LED Color State Description
PNIO1 LED “Link” Green On ETHERNET connection established
Off No ETHERNET connection
PNIO1 LED “RX/TX” Yellow On
Blinking Device sends/receives frames
Off
PNIO2 LED “Link” Green On ETHERNET connection established
Off No ETHERNET connection
PNIO2 LED “RX/TX” Yellow On
Blinking Device sends/receives frames
Off