Technical DataΒΆ
The System Data of AC500-eCo apply System Data AC500-eCo
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Process supply voltage UP | ||
Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) | |
Rated value | 24 V DC | |
Current consumption | 0.04 A | |
Inrush current (at power-up) | 0.05 A:sup:2s | |
Max. ripple | 5 % | |
Protection against reversed voltage | Yes | |
Protection fuse for UP | Recommended | |
Current consumption from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | Ca. 5 mA | |
Galvanic isolation | Yes, between the input group and the rest of the module | |
Isolated groups | 1 (2 channels per group) | |
Surge-voltage (max.) | 35 V DC for 0.5 s | |
Max. power dissipation within the module | 1.1 W | |
Weight | Ca. 120 g | |
Mounting position | Horizontal or vertical | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Attention
:strong:Attention:
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.