Technical Data of the Analog Inputs

Parameter Value
Number of channels per module 2 configurable RTD (resistance temperature detector) inputs
Distribution of channels into groups 1 (2 channels per group)
Resolution  
  RTD 0.1 °C / 0.1 °F
  Resistance 15 bits + sign
Connection of the signals O0+ and O1+ Terminals 10 and 13
Connection of the signals I0- and I1- Terminals 11 and 14
Connection of the signals I0+ and I1+ Terminals 12 and 15
Input type Module ground referenced RTD for 2-wire and 3-wire resistance temperature detectors
Galvanic isolation Against internal power supply and other modules
Input ranges Pt100, Pt1000, Ni100, Ni1000
150 W, 300 W
Indication of the input signals No
Module update time All channels: < 1 s
Channel input resistance > 100 kW
Input filter attenuation -3 dB at 3.6 kHz
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

Depending on RTD max. ± 0.6 % of full scale (guaranteed for 3-wires connection only)

at 25 °C

Max.

± 2 % of full scale (guaranteed for 3-wires connection only)

at 0 … 60 °C or EMC disturbances

Measuring range Table AI562 - Analog Input Module
Analog to digital conversion time Typ. 140 ms per channel
Unused inputs Can be left open and should be configured as “unused”
Input data length 4 bytes
Power dissipation inside the sensor (max.) 1 mW
Suppression of interference On request
Maximum input voltage 30 V DC (sense), 5 V DC (source)
Basic error (resistance) 0.1 % of full-scale
Repeatability 0.05 % of full-scale
Overvoltage protection Yes, up to 30 V DC
Wire loop resistance < 20 W
Max. cable length (conductor cross section > 0,14 mm²)  
  Unshielded wire 10 m
  Shielded wire 100 m