Technical Data of the Relay Outputs

Parameter Value
Number of channels per module 8 relay outputs
Distribution of channels into groups 8 groups of 1 channel each
Connection of the channel R0 Terminal 2.0 (common), 3.0 (NO) and 4.0 (NC)
Connection of the channel R1 Terminal 2.1 (common), 3.1 (NO) and 4.1 (NC)
Connection of the channel R6 Terminal 2.6 (common), 3.6 (NO) and 4.6 (NC)
Connection of the channel R7 Terminal 2.7 (common), 3.7 (NO) and 4.7 (NC)
Galvanic isolation Between the channels and from the rest of the module
Indication of the output signals One yellow LED per channel, the LED is ON when the relay coil is energized
Way of operation Non-latching type
Output delay (0->1 or 1->0) On request
Output data length 1 byte
Relay power supply By UP process voltage
Relay outputs  
  Output short-circuit protection Should be provided externally with a fuse or circuit breaker
Rated protection fuse 6 A gL/gG per channel
Min. switching current 10mA
Output switching capacity  
  Resistive load, max. 3 A; 3 A (230 V AC), 2 A (24 V DC)
  Inductive load, max. 1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC)
  Lamp load 60 W (230 V AC), 10 W (24 V DC)
Output switching capacity (XC version above 60 °C) On request
Life time (cycles)

Mechanical: 300 000;

Under load: 300 000 (24 V DC at 2 A), 200 000 (120 V AC at 2 A), 100 000 (230 V AC at 3 A)

Spark suppression with inductive AC load Must be performed externally according to driven load specifications
Demagnetization with inductive DC load A free-wheeling diode must be circuited in parallel to the inductive load
Switching frequency  
  With resistive load Max. 10 Hz
  With inductive load Max. 2 Hz
  With lamp load On request
Max. cable length  
  Shielded 1000 m
  Unshielded 600 m