Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Process supply voltage UP | ||
Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP) | |
Rated value | 24 V DC | |
Max. ripple | 5 % | |
Protection against reversed voltage | Yes | |
Rated protection fuse on UP | 10 A fast | |
Galvanic isolation | Yes, per module | |
Current consumption | ||
From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | ca. 2 mA | |
From UP at normal operation / with outputs | 0.05 A + output loads | |
Inrush current from UP (at power up) | 0.010 A²s | |
Max. power dissipation within the module | 6 W (outputs OFF) | |
Weight (without terminal unit) | ca. 300 g | |
Mounting position | Horizontal or vertical with derating (output load reduced to 50 % at 40 °C per group) | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Attention
:strong:Attention:
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.