Electrical Connection

The electrical connection of the I/O channels is carried out using the 40 terminals of the I/O terminal unit. I/O modules can be replaced without re-wiring the terminal units.

The terminals 1.8 to 4.8 and 1.9 to 4.9 are electrically interconnected within the I/O terminal unit and have always the same assignment, independent of the inserted module:

Terminals 1.8 to 4.8: process voltage UP = +24 VDC

Terminals 1.9 to 4.9: process voltage ZP = 0 V

The assignment of the other terminals:

Terminals Signal Description
1.0 to 1.7 O0 to O7 8 digital outputs
2.0 to 2.7 O8 to O15 8 digital outputs
3.0 to 3.7 O16 to O23 8 digital outputs
4.0 to 4.7 O24 to O31 8 digital outputs

The internal power supply voltage for the module’s circuitry is carried out via the I/O bus (provided by a bus module or a CPU). Thus, the current consumption from 24 VDC power supply at the terminals L+/UP and M/ZP of the CPU/bus module increases by 2 mA per DO524.

The external power supply connection is carried out via the UP (+24 VDC) and the ZP (0 VDC) terminals.

Attention

:strong:Risk of damaging the PLC modules!

Overvoltages and short circuits might damage the PLC modules.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you begin with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.

The following block diagram shows the internal construction of the digital outputs:

../_images/8f5d85009022005f0a3313904d4ee33c

The module provides several diagnosis functions DO524 - Digital Output Module.