FunctionalityΒΆ
Digital outputs | 32 (24 VDC) |
LED displays | For signal states, errors and supply voltage |
Internal power supply | Via the expansion bus interface (I/O bus) |
External power supply | Via the terminals ZP and UP (process voltage 24 VDC) |
Required terminal unit | TU515 or TU516 TU515, TU516, TU516-H and TU542 for I/O Modules |
The device is plugged on a terminal unit TU515, TU516, TU516-H and TU542 for I/O Modules. Position the module properly and press until it locks in place. The terminal unit is either mounted on a DIN rail or to the wall using 2 screws plus the additional accessory for wall mounting (TA526 TA526 - Wall Mounting Accessory).
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.