FunctionalityΒΆ

Digital outputs 32 (24 VDC)
LED displays For signal states, errors and supply voltage
Internal power supply Via the expansion bus interface (I/O bus)
External power supply Via the terminals ZP and UP (process voltage 24 VDC)
Required terminal unit TU515 or TU516 TU515, TU516, TU516-H and TU542 for I/O Modules

The device is plugged on a terminal unit TU515, TU516, TU516-H and TU542 for I/O Modules. Position the module properly and press until it locks in place. The terminal unit is either mounted on a DIN rail or to the wall using 2 screws plus the additional accessory for wall mounting (TA526 TA526 - Wall Mounting Accessory).

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.