Measuring Ranges

Note

AI563 needs 4 seconds for initialization after applying the process supply voltage to clamp UP/ZP. During these 4 seconds, the measurement values are set to ‘0’. After that, valid measurement values are provided by the module.

After an interruption of the process supply voltage > 10 ms, a re-initialization is performed by AI563.

Note

:strong:Risk of invalid analog input values!

The analog input values may be invalid if the measuring range of the inputs is exceeded.

Make sure that the analog signal at the connection terminals is always within the signal range.

Note

When a wire break occurs on a sensor wire, the temperature measurement value of the corresponding channel changes to Overflow (Hexadecimal 7FFF).

Range

Type J

-210 … +1200 °C

Type K

-270 … +1372 °C

Type N

-270 … +1300 °C

Type T

-270 … +400 °C

Digital value
          Decimal Hex.
Overflow > 1200.0 °C > 1372.0 °C > 1300.0 °C > 400.0 °C 32767 7FFF
Normal range         17680 4510
  1372.0 °C     13720 3598
  : 1300.0 °C   13000 32C8
1200.0 °C : :   12000 2EE0
: : : 400.0 °C 4000 0FA0
: : : : : :
0.1 °C 0.1 °C 0.1 °C 0.1 °C 1 1
0.0 °C 0.0 °C 0.0 °C   0 0000
-0.1 °C -0.1 °C -0.1 °C -0.1 °C -1 FFFF
: : : : : :
: : : : -500 FE0C
-210.0 °C : : : -2100 F7CC
  -270.0 °C -270.0 °C -270.0 °C -2700 F574
Underflow < -210.0 °C < -270.0 °C < -270.0 °C < -270.0 °C -32768 8000
Range -80 mV … +80 mV

Type E

-270 … +1000 °C

Types R, S

-50 … +1768 °C

Digital value
        Decimal Hex.
Overflow > +90 mV > 1000.0 °C > 1768.0 °C 32767 7FFF
Normal range +80 mV     27648 6C00
    1768.0 °C 17680 4510
  1000.0 °C   10000 2710
      9000 2328
: : : : :
3 µV 0.1 °C 0.1 °C 1 1
0 µV 0.0 °C 0.0 °C 0 0000
-3 µV -0.1 °C -0.1 °C -1 FFFF
: : : : :
: : -50.0 °C -500 FE0C
: -270.0 °C   -2700 F574
-80 mV     -27648 9400
Underflow < -90 mV < -270.0 °C < -50.0 °C -32768 8000