Electrical Connection

Note

After powering up the system, input channels, which are configured will have undefined values /diagnosis message for typically 45 seconds, if the wires of all configured channels are broken.

The analog input module AI563 can be connected to the following devices via the I/O bus connector:

  • S500 bus modules (e. g. CI592-CS31, CI501-PNIO, CI541-DP, CI581-CN)
  • AC500 CPUs (PM5xx)
  • other AC500 I/O modules

Note

The I/O module must not be used as a decentralized communication interface module with DC505-FBP and CI590-CS31-HA bus modules.

Note

If the AI563 is connected to a PROFINET Bus Module, the firmware version of PROFINET Bus Modules must be 1.2 or above.

Note

For a detailed description of the mounting, disassembly and electrical connection of the module, please refer to the System Assembly chapter AC500-eCo.

The electrical connection is carried out by using a removable 9-pin and 11-pin terminal block. These terminal blocks differ in their connection system (spring terminals or screw-type terminals, cable mounting from the front or from the side). TA563-TA565 - Terminal Blocks. The terminal blocks are not included in the module’s scope of delivery and must be ordered separately.

The following block diagram shows the internal construction of the analog inputs:

../_images/7801ce625c9a6bd80a3313901d97dd32

The assignment of the terminals:

Terminal Signal Description
1 I0+ Plus pole of channel 0
2 I0- Minus pole of channel 0
3 I1+ Plus pole of channel 1
4 I1- Minus pole of channel 1
5 I2+ Plus pole of channel 2
6 I2- Minus pole of channel 2
7 I3+ Plus pole of channel 3
8 I3- Minus pole of channel 3
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 SG Signal ground
16 SG Signal ground
17 SG Signal ground
18 SG Signal ground
19 UP Process voltage UP (24 VDC)
20 ZP Process voltage ZP (0 VDC)

The internal power supply voltage for the module’s circuitry is carried out via the I/O bus (provided by a bus module or a CPU). Thus, the current consumption from 24 VDC power supply at the terminals UP/L+ and ZP/M of the CPU/bus module increases by 5 mA per AI563.

The external power supply connection is carried out via the UP (+24 VDC) and the ZP (0 VDC) terminals.

Attention

:strong:Risk of imprecise and faulty measurements!

Analog signals may be distorted seriously by external electromagnetic influences.

Use shielded wires when wiring analog signal sources. The cable shield must be grounded at both ends of the cable. Provide a potential equalisation of a low resistance to avoid high potential differences between different parts of the plant.

Attention

:strong:Risk of damaging the PLC modules!

The PLC modules must not be removed while the plant is connected to a power supply.

Make sure that all voltage sources (supply and process voltage) are switched off before you

  • connect or disconnect any signal or terminal block
  • remove or replace a module.

Attention

:strong:Risk of damaging the PLC modules!

Overvoltages and short circuits might damage the PLC modules.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you begin with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.

The module provides several diagnosis functions AI563 - Analog Input Module.

The following figure shows the electrical connection of thermocouples to the inputs of the module:

../_images/ced3110d5c9a463e0a33139003c60c04

The meaning of the LEDs is described in Displays AI563 - Analog Input Module chapter.