State LEDs¶
During the power ON procedure, the module initializes automatically. All LEDs (except the channel LEDs) are ON during this time.
LED | State | Color | LED = OFF | LED = ON | LED flashes |
---|---|---|---|---|---|
Inputs 00…07 |
Digital input | Yellow | Input = OFF | Input = ON (the input voltage is even displayed if the supply voltage is OFF). | – |
Outputs 08…15 (relays) | Digital output | Yellow | Relay output = OFF | Relay output = ON | – |
UP | Process supply voltage 24 VDC via terminal | Green | Process supply voltage is missing | Process supply voltage OK | – |
CH-ERR1 | Channel Error, error messages in groups (digital inputs/outputs combined into the groups 1 and 2) | Red | No error or process supply voltage is missing | Severe error within the corresponding group | Error on one channel of the corresponding group |
CH-ERR2 | Red | ||||
CH-ERR *) | Module Error | Red | – | Internal error | – |
*) All of the LEDs CH-ERR1 to CH-ERR2 light up together |