Connection of Passive-type Analog Sensors (Current)

The following figure shows the connection of passive-type analog sensors (current).

../_images/10cc34286b0d325d0a3313907ac0d0a2

Connection of passive-type analog sensors (current)

Current 4…20 mA 1 channel used

The measuring ranges are described in the section Measuring Ranges CI511-ETHCAT CI511-ETHCAT.

Caution

If, during initialization, an analog current sensor supplies more than 25 mA for more than 1 second into an analog input, this input is switched off by the module (input protection). In such cases, it is recommended, to protect the analog input by a 10-volt zener diode (in parallel to I+ and I-). But, in general, it is a better solution to prefer sensors with fast initialization or without current peaks higher than 25 mA.

Unused input channels can be left open-circuited, because they are of low resistance.