Connection of Active-type Analog Sensors (Voltage) with no Electrically \ Isolated Power Supply¶
The following figure shows the connection of active-type sensors (voltage) with no electrically isolated power supply.
Connection of active-type sensors (voltage) with no electrically isolated power supply
Attention
:strong:Risk of faulty measurements!
The negative pole/earthing potential at the sensors must not have too large a potential difference with respect to ZP (max. ± 1 V within the full signal range).
Make sure that the potential difference never exceeds ± 1 V.
Voltage | 0…10 V | 1 channel used |
Voltage | -10 V…+10 V *) | 1 channel used |
*) if the sensor can provide this signal range
The measuring ranges are described in the section Measuring Ranges CI511-ETHCAT CI511-ETHCAT.
In order to avoid error messages or long processing times, it is useful to configure unused analog input channels as “unused”.