Functionality

4 analog inputs, individually \ configurable for

  • Unused (default setting)
  • 0…10 V
  • -10 V…+10 V
  • 0…20 mA
  • 4…20 mA
  • Pt100, -50 °C…+400 °C (2-wire)
  • Pt100, -50 °C…+400 °C (3-wire), requires 2 channels
  • Pt100, -50 °C…+70 °C (2-wire)
  • Pt100, -50 °C…+70 °C (3-wire), requires 2 channels
  • Pt1000, -50 °C…+400 °C (2-wire)
  • Pt1000, -50 °C…+400 °C (3-wire), requires 2 channels
  • Ni1000, -50 °C…+150 °C (2-wire)
  • Ni1000, -50 °C…+150 °C (3-wire), requires 2 channels
  • 0…10 V with differential inputs, requires 2 channels
  • -10 V…+10 V with differential inputs, requires 2 channels
  • Digital signals (digital input)

4 analog outputs, individually configurable \ for

  • Unused (default setting)
  • -10 V…+10 V
  • 0…20 mA
  • 4…20 mA
Parameter Value
Resolution of the analog channels  
  Voltage -10 V… +10 V 12 bits plus sign
  Voltage 0…10 V 12 bits
  Current 0…20 mA, 4…20 mA 12 bits
  Temperature 0.1 °C
LED displays 11 LEDs for signals and error messages
Internal power supply Via the expansion bus interface (I/O bus)
External power supply Via the terminals ZP and UP (process voltage 24 VDC)
Required Terminal Unit TU515 or TU516 TU515, TU516, TU516-H and TU542 for I/O Modules