Mounting and Demounting the Terminal Unit

Mounting on DIN rail

  1. Mount DIN rail 7.5 mm or 15 mm.

  2. Mount the Terminal Unit.

    The Terminal Unit is snapped into the DIN rail in the same way as the Terminal Base. Once secured to the DIN rail, slide the Terminal Unit to the left until it fully locks into place creating a solid mechanical and electrical connection.

    Note

    When attaching the devices, make sure the bus connectors are securely locked together to ensure proper electrical connection. Max. 10 Terminal Units can be attached.

    ../_images/88ce2b14e918f4990a317f345b6d2f4f
  3. Demounting: A screwdriver is inserted in the indicated place to separate the Terminal Units.

    ../_images/bb00d509e919a9260a317f34483308e7

Mounting with Screws

If the Terminal Unit should be mounted with screws, Wall Mounting Accessories TA526 TA526 - Wall Mounting Accessory must be inserted at the rear side first. These plastic parts prevent bending of the Terminal Base while screwing on.

../_images/6dea6751e919aaac0a317f3458f56d11

Fastening with screws

Note

By wall mounting, the Terminal Unit is earthed through the screws. It is necessary that

  • the screws have a conductive surface (e.g. steel zinc-plated or brass nickel-plated)
  • the mounting plate is earthed
  • the screws have a good electrical contact to the mounting plate

Practical Tip

The following procedure allows you to use the mounted modules as a template for drilling holes in the panel. Due to module mounting hole tolerance, it is important to follow these procedures:

  1. On a clean work surface, mount no more than 3 modules (e.g. one Terminal Base and two Terminal Units).

  2. Using the mounted modules as a template, carefully mark the center of all module-mounting holes on the panel.

  3. Return the mounted modules to the clean work surface, including any previously mounted modules.

  4. Drill and tap the mounting holes for the screws (M4 or #8 recommended).

  5. Place the modules back on the panel and check for proper hole alignment.

  6. Attach the modules to the panel using the mounting screws.

    Note

    If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.

  7. Repeat the steps for all remaining modules.