Mounting/Demounting Terminal Bases and Function Module Terminal Bases

Demounting on DIN rail

  1. Mount DIN rail 7.5 mm or 15 mm.

  2. Mount the Terminal Base/Function Module Terminal Base:

    ../_images/88ce2b14e918f4990a317f345b6d2f4f

    The Terminal Base is put on the DIN rail above and then snapped-in below.

  3. The demounting is carried out in a reversed order.

    ../_images/743be974e918b9fa0a317f342dd3b453

Mounting with Screws

If the Terminal Base should be mounted with screws, Wall Mounting Accessories TA526 TA526 - Wall Mounting Accessory must be inserted at the rear side first. These plastic parts prevent bending of the Terminal Base while screwing on. TB51x needs one TA526, TB52x and TB54x need two TA526.

../_images/69de1406e91834e40a317f347dcd2692

Terminal Bases, Fastening with screws

../_images/6fa7cffde9193e160a317f346b9b3233

Function Module Terminal Bases, Fastening with screws

Note

By wall mounting, the Terminal Base is earthed through the screws. It is necessary that

  • the screws have a conductive surface (e.g. steel zinc-plated or brass nickel-plated)
  • the mounting plate is earthed
  • the screws have a good electrical contact to the mounting plate

Practical Tip

The following procedure allows you to use the mounted modules as a template for drilling holes in the panel. Due to module mounting hole tolerance, it is important to follow these procedures:

  1. On a clean work surface, mount no more than 3 modules (e.g. one Terminal Base and two Terminal Units).

  2. Using the mounted modules as a template, carefully mark the center of all module-mounting holes on the panel.

  3. Return the mounted modules to the clean work surface, including any previously mounted modules.

  4. Drill and tap the mounting holes for the screws (M4 or #8 recommended).

  5. Place the modules back on the panel and check for proper hole alignment.

  6. Attach the modules to the panel using the mounting screws.

    Note

    If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.

  7. Repeat the steps for all remaining modules.