Group Parameters for the Digital Part

Name Value Internal value Internal value, type Default
Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

BYTE

0.1 ms

0x00

Detect short circuit at outputs

Off

On

0

1

BYTE

On

0x01

Behavior digital outputs at communcation error 1)

Off

Last value

Last value 5 sec

Last value 10 sec

Substitute value

Substitute value 5 sec

Substitute value 10 sec

0

1

6

11

2

7

12

BYTE

Off

0x00

Substitute value at output 0 … 255 00h … FFh BYTE

0

0x00

Detect voltage overflow at outputs 2)

Off

On

0

1

BYTE

Off

0x00

1) The parameter Behavior digital outputs at communcation error is only analyzed if the failsafe mode is ON.

2) The state “externally voltage detected” appears if the output of a channel DC0..DC7 is to be switched on while an external voltage is connected CI581-CN. In this case, the start-up is disabled as long as the external voltage is connected. The monitoring of this state and the resulting diagnosis message can be disabled by setting the parameters to “OFF”.