Channel \ Parameters for the Analog Outputs (2x)

Name Value Internal value Internal value, type Default
Output 0, Channel configuration Operation modes of analog outputs Operation modes of analog outputs BYTE 0
Output 0, Check channel Channel monitoring Channel monitoring BYTE 0
Output 0, Substitute value Substitute value Substitute value WORD 0
Output 1, Channel configuration Operation modes of analog outputs Operation modes of analog outputs BYTE 0
Output 1, Check channel Channel monitoring Channel monitoring BYTE 0
Output 1, Substitute value Substitute value Substitute value WORD 0
Channel Configuration - Operating Modes of the Analog Outputs
Internal value Operating Modes (individually configurable)
0 (default) Not used
128 -10 V…+10 V
129 0…20 mA
130 4…20 mA
Channel Monitoring
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Substitute Value
Intended Behavior of Output Channel  when the Control System Stops Required Setting of the Module Parameter “Behavior of Outputs in Case of a Communication Error” Required Setting of the Channel Parameter “Substitute value”
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then turn off Last value 5 sec 0
Last value for 10 s and then turn off Last value 10 sec 0
Substitute value infinite Substitute value Depending on configuration
Substitute value for 5 s and then turn off Substitute value 5 sec Depending on configuration
Substitute value for 10 s and then turn off Substitute value 10 sec Depending on configuration