Connection of Resistance Thermometers in 3-wire Configuration to the \ Analog Inputs

When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the module CI581-CN provides a constant current source which is multiplexed over the max. 4 analog input channels.

The following figure shows the connection of resistance thermometers in 3-wire configuration to the analog inputs AI0 and AI1. Proceed with the analog inputs AI2 and AI3 in the same way.

../_images/7624a52961962bdb0a33139065fb3e71

Connection of resistance thermometers in 3-wire configuration to the analog inputs

With 3-wire configuration, 2 adjacent analog channels belong together (e. g. the channels 0 and 1). In this case, both channels are configured according to the desired operating mode. The lower address must be the even address (channel 0), the next higher address must be the odd address (channel 1).

The constant current of one channel flows through the resistance thermometer. The constant current of the other channel flows through one of the cores. The module calculates the measured value from the two voltage drops and stores it under the input with the higher channel number (e. g. I1).

In order to keep measuring errors as small as possible, it is necessary to have all the involved conductors in the same cable. All the conductors must have the same cross section.

Pt100 3-wire configuration, 2 channels used
Pt1000 3-wire configuration, 2 channels used
Ni1000 3-wire configuration, 2 channels used

For the measuring ranges that can be configured, please refer to the sections Measuring Ranges CI581-CN and Parameterization CI581-CN.

The module CI581-CN performs a linearization of the resistance characteristic.

To avoid error messages, configure unused analog input channels as “unused”.