Connection of Resistance Thermometers in 2-wire Configuration to the \ Analog Inputs¶
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow to build the necessary voltage drop for the evaluation. For this, the module CI581-CN provides a constant current source which is multiplexed over the max. 4 analog input channels.
The following figure shows the connection of resistance thermometers in 2-wire configuration to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Connection of resistance thermometers in 2-wire configuration to the analog inputs
Pt100 | 2-wire configuration, 1 channel used |
Pt1000 | 2-wire configuration, 1 channel used |
Ni1000 | 2-wire configuration, 1 channel used |
For the measuring ranges that can be configured, please refer to sections Measuring Ranges CI581-CN and Parameterization CI581-CN.
The module CI581-CN performs a linearization of the resistance characteristic.
To avoid error messages, configure unused analog input channels as “unused”.