Channel \ parameters for the Analog Inputs (4x)

Name Value Internal value Internal value, type Default
Input 0, Channel configuration Operation modes of analog inputs Operation modes of analog inputs BYTE 0
Input 0, Check channel Settings channel monitoring Settings channel monitoring BYTE 0
: : : : :
: : : : :
Input 3, Channel configuration Operation modes of analog inputs Operation modes of analog inputs BYTE 0
Input 3, Check channel Settings channel monitoring Settings channel monitoring BYTE 0
Channel Configuration - Operating Modes of the Analog Inputs
Internal Value Operating Modes (individually configurable)
0 (default) Not used
1 0…10 V
2 Digital input
3 0…20 mA
4 4…20 mA
5 -10 V…+10 V
8 2-wire Pt100 -50…+400 °C
9 3-wire Pt100 -50…+400 °C  *)
10 0…10 V (voltage diff.)  *)
11 -10 V…+10 V (voltage diff.)  *)
14 2-wire Pt100 -50…+70 °C
15 3-wire Pt100 -50…+70 °C  *)
16 2-wire Pt1000 -50…+400 °C
17 3-wire Pt1000 -50…+400 °C  *)
18 2-wire Ni1000 -50…+150 °C
19 3-wire Ni1000 -50…+150 °C  *)
*) In the operating modes with 3-wire configuration or with differential inputs, two adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are configured in the desired operating mode. The lower address must be the even address (channel 0). The next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1).
Channel Monitoring
Internal Value Check Channel
0 (default) Plausib(ility), cut wire, short circuit
3 Not used