Buffer Parameters (to Be Configured for Each Used Buffer)ΒΆ

Name Value Internal value Internal value, type Default
Identifier 0..2047 (CAN2A) 0..2047 (CAN2A) WORD (CAN2A) 0
0..536870911 (CAN2B) 0..536870911 (CAN2B) DWORD (CAN2B)
Receive buffer size (size in numbers of telegrams) 1..32 1..32 BYTE 1
Behaviour on receive buffer overflow *) Overwrite 0 BYTE 0
Discard 1
Overwrite and send diagnostics (PROFINET alarm) 3
Discard and send diagnostics (PROFINET alarm) 4
*) The following table describes the values in detail.
Setting Description
Overwrite The oldest buffer entry which is stored in the buffer is overwritten with the new incoming telegram.
Discard The new incoming telegram is discarded.
Overwrite and send diagnostics (PROFINET alarm) The oldest buffer entry which is stored in the buffer is overwritten with the new incoming telegram. Additionally, a PROFINET alarm (diagnostic) will be sent to inform the user of the overflow occurrence.
Discard and send diagnostics (PROFINET alarm) The new incoming telegram is discarded. Additionally a PROFINET alarm (diagnostic) will be sent to inform the user of the overflow occurrence.

Note

Up to 64 buffers are allowed to be configured for each CAN2A and CAN2B type, each buffer containing the parameters described above.