Minimal StructureΒΆ

A control station with an ETHERNET interface is connected to a substation with an ETHERNET interface.

../_images/acce485e65c0b9540a317f342699c04d
Control station
Substation

Configuration at the control station (PM57x-/ PM58x-/ PM59x-ETH, PM5650-2ETH)

The respective substation IP address must be specified at the control station. For this, in the network settings of the control station (1) enter the IP address of the substation (in the example: 192.168.1.25). Option Enable redundant connection must be disabled.

Configuration at the substation (PM57x-/ PM58x-/ PM59x-ETH, PM5650-2ETH)

Either the control station IP address or the general address 0.0.0.0 must be specified at the substation (2). For this, in the network settings of the substation enter the IP address of the control station (in the example: 192.168.1.10). Option Enable redundant connection must be disabled.

Note

If the general address 0.0.0.0 is used at the substation, no further control station can be configured on this controller for a further substation.