Network Redundancy with 1 Network and 1 ETHERNET Port in Substation¶
Note
No online redundancy.
Only one connection will be established.
Control station with 2 paths to reach substation | |
1 Substation with 1 ETHERNET interface |
Configuration at the control stations (PM591-2ETH, PM595-4ETH, PM5650-2ETH)
The substation’s IP addresses must be specified at the control stations (1). For this, in the network settings of the control station enter the IP addresses of the substation (in the example: 192.168.1.25 and 0.0.0.0). Option Enable redundant connection must be disabled.
Configuration at the substation (PM591-2ETH, PM595-4ETH, PM5650-2ETH)
Either the control station’s IP addresses or the general address 0.0.0.0 must be specified at the substation (2). For this, in the network settings of the substation enter the IP addresses of the control station (in the example: 192.168.1.10 and 192.168.2.11). Option Enable redundant connection must be enabled.
Note
If the general address 0.0.0.0 is used at the substation, no further control station on another substation can be configured on this controller. Equally, the substation connection must be activated for both interfaces.