Connection of the configurable digital inputs/outputs¶
The following figure shows the electrical connection of the configurable digital input/output DC16 and DC17. DC16 is connected as an input and DC17 is connected as an output. Proceed with the configurable digital inputs/outputs DC18 to DC23 in the same way.
Connection of configurable digital inputs/outputs to the module DA502
Attention
:strong:Risk of influences to the connected sensors!
Some sensors may be influenced by the deactivated module outputs of DA502.
Connect a 470 Ω / 1 W resistor in series to inputs DC16/DC17 if using them as Fast Counter inputs to safely avoid any influences.
The meaning of the LEDs is described in Displays Digital/Analog Input/Output Module DA502 chapter.