Technical Data of the Relay OutputsΒΆ
Number of channels per module | 4 relay outputs |
Distribution of channels into groups | 4 groups of 1 channel each |
Connection of the four relays | See figure Electrical Connection Digital Input/Output Module DX531 |
Electrical isolation | Between the channels and from the rest of the module |
Indication of the output signals | 1 yellow LED per channel, the LED is ON when the relay coil is energized |
Output delay (0->1 or 1->0) | On request |
Relay power supply | By UP process voltage |
Relay outputs | |
output short-circuit protection | Must be provided externally with a fuse or circuit breaker |
rated protection fuse | 6 A gL/gG per channel |
Output switching capacity | |
resistive load, max. | 3 A; 3 A (230 V AC), 2 A (24 V DC) |
inductive load, max. | 1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC) |
lamp load | 60 W (230 V AC), 10 W (24 V DC) |
Life time (cycles) | Mechanical: 300 000; Under load: 300 000 (24 V DC at 2 A), 200 000 (120 V AC at 2 A), 100 000 (230 V AC at 3 A) |
Spark suppression with inductive AC load | Must be performed externally according to driven load specifications |
Demagnetization with inductive DC load | A free-wheeling diode must be circuited in parallel to the inductive load |
Switching frequency | |
with resistive load | Max. 10 Hz |
with inductive load | Max. 2 Hz |
with lamp load | On request |
Max. cable length | |
shielded | 1000 m |
unshielded | 600 m |