Electrical Connection

The PROFINETâ Bus Module CI504-PNIO is plugged on the Terminal Unit TU520-ETH PROFINET:sup:® IO Terminal Unit TU520-ETH for PROFINET® IO Bus Modules. Properly seat the module and press until it locks in place. The Terminal Unit is mounted on a DIN rail or with 2 screws plus the additional accessory for wall mounting (TA526 Wall Mounting Accessory TA526).

The electrical connection of the power supply voltage is carried out using the 6 terminals and the 3 removable connectors of the Terminal Unit. The CI504-PNIO can be replaced without re-wiring the Terminal Units.

Note

Mounting, disassembling and electrical connection for the Terminal Units and the I/O modules are described in detail in S500 System Data System Data AC500.

The terminals 1.0, 2.0 and 3.0 as well as 1.1, 2.1 and 3.1 are electrically interconnected within the Terminal Unit and have always the same assignment, independent of the inserted module:

Assignment of the terminals:
Terminal Signal Meaning
1.0 UP Process voltage UP (+24 V DC)
1.1 ZP Process voltage ZP (0 V DC)
2.0 UP Process voltage UP (+24 V DC)
2.1 ZP Process voltage ZP (0 V DC)
3.0 UP Process voltage UP (+24 V DC)
3.1 ZP Process voltage ZP (0 V DC)
Assignment of the terminals of removable connectors X11, X12 \ and X13 (Serial Interfaces):
Terminal Signal Meaning
1 Term-P RS-485 Internal line terminating resistor for non-inverted signal (Rx/Tx-P)
RS-422 Non-inverted receive signal terminal (RxD+)
2 Rx/Tx-P RS-485 Non-inverted I/O signal terminal for each channel
RS-422 Non-inverted transmit signal terminal (TxD+)
3 Rx/Tx-N RS-485 Inverted I/O signal terminal for each channel
RS-422 Inverted transmit signal terminal (TxD-)
4 Term-N RS-485 Internal line-terminating-resistor for inverted signal (Rx/Tx-N) terminal
RS-422 Inverted receive signal terminal (RxD-)
5 RTS RS-232 Request To Send signal terminal for each channel
6 TxD RS-232 Transmit signal terminal for each channel
7 SGND RS-232 Signal ground for each channel
8 RxD RS-232 Receive signal terminal for each channel
9 CTS RS-232 Clear To Send signal terminal for each channel

Note

The connection of SGND (ground) is optional for RS-485/RS-422.

Note

For RS-422, no external line-terminating resistors have to connected. They are already connected inside the module.

Caution

:strong:Risk of damaging the modules!

The modules must not be removed when the plant is powered on.

Make sure that all voltage sources (supply and process voltage) are switched off before you are removing or replacing a module.

Caution

:strong:Risk of damaging the modules!

The modules can be damaged by overvoltages and short circuits.

Make sure that all voltage sources (supply and process voltage) are switched off before you are beginning with operations at the system.

The module provide several diagnosis functions PROFINETâ IO Bus Module CI504-PNIO.