Technical Data of the Module

Process supply voltages UP/UP3  
Rated value 24 V DC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Electrical isolation CANopen® interface against the rest of the module
Inrush current from UP (at power up) On request
Current consumption via UP (normal operation) 0.2 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections

Terminals 2.8 and 3.8 for +24 V (UP)

Terminal 4.8 for +24 V (UP3)

Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)

Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of analog inputs 4
Number of analog outputs 2
Reference potential for all digital inputs and outputs Minus pole of the supply voltage, signal name ZP
Setting of the CANopen® Node ID identifier With 2 rotary switches at the front side of the module
Diagnose See Diagnosis CANopenâ Bus Module CI582-CN
Operation and error displays 34 LEDs (totally)
Weight (without Terminal Unit) Ca. 125 g
Mounting position

Horizontal

Or vertical with derating (output load reduced to 50 % at 40 °C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.