Technical Data of the Module¶
Process supply voltages UP/UP3 | |
Rated value | 24 V DC (for inputs and outputs) |
Max. load for the terminals | 10 A |
Protection against reversed voltage | Yes |
Rated protection fuse on UP/UP3 | 10 A fast |
Electrical isolation | CANopen® interface against the rest of the module |
Inrush current from UP (at power up) | On request |
Current consumption via UP (normal operation) | 0.2 A |
Current consumption via UP3 | 0.06 A + 0.5 A max. per output |
Connections | Terminals 2.8 and 3.8 for +24 V (UP) Terminal 4.8 for +24 V (UP3) Terminals 2.9, 3.9 and 4.9 for 0 V (ZP) |
Max. power dissipation within the module | 6 W |
Number of digital inputs | 8 |
Number of digital outputs | 8 |
Number of analog inputs | 4 |
Number of analog outputs | 2 |
Reference potential for all digital inputs and outputs | Minus pole of the supply voltage, signal name ZP |
Setting of the CANopen® Node ID identifier | With 2 rotary switches at the front side of the module |
Diagnose | See Diagnosis CANopenâ Bus Module CI582-CN |
Operation and error displays | 34 LEDs (totally) |
Weight (without Terminal Unit) | Ca. 125 g |
Mounting position | Horizontal Or vertical with derating (output load reduced to 50 % at 40 °C per group) |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Note
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.