Technical DataΒΆ
The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.
Process supply voltage UP | |
Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) |
Rated value | 24 V DC |
Current consumption via UP terminal | 20 mA + max. 0.5 A per output |
Max. ripple | 5 % |
Inrush current | 0.000002 A:sup:2s |
Protection against reversed voltage | Yes |
Rated protection fuse for UP | Recommended; the outputs must be protected by an 3 A fast fuse |
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module | Ca. 10 mA |
Electrical isolation | Yes, between the output group and the rest oft module |
Isolated groups | 1 (16 channels per group) |
Surge-voltage (max.) | 35 V DC for 0.5 s |
Max. power dissipation within the module | 1.4 W |
Weight | Ca. 125 g |
Mounting position | Horizontal or vertical |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |