Technical DataΒΆ
The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.
| Process supply voltage UP | |
| Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) | 
| Rated value | 24 V DC | 
| Current consumption via UP terminal | 20 mA + max. 0.5 A per output | 
| Max. ripple | 5 % | 
| Inrush current | 0.000002 A:sup:2s | 
| Protection against reversed voltage | Yes | 
| Rated protection fuse for UP | Recommended; the outputs must be protected by an 3 A fast fuse | 
| Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module | Ca. 10 mA | 
| Electrical isolation | Yes, between the output group and the rest oft module | 
| Isolated groups | 1 (16 channels per group) | 
| Surge-voltage (max.) | 35 V DC for 0.5 s | 
| Max. power dissipation within the module | 1.4 W | 
| Weight | Ca. 125 g | 
| Mounting position | Horizontal or vertical | 
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |