Technical DataΒΆ

The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.

Process supply voltage UP  
Connections Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V)
Rated value 24 V DC
Current consumption via UP terminal 20 mA + max. 0.5 A per output
Max. ripple 5 %
Inrush current 0.000002 A:sup:2s
Protection against reversed voltage Yes
Rated protection fuse for UP Recommended; the outputs must be protected by an 3 A fast fuse
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module Ca. 10 mA
Electrical isolation Yes, between the output group and the rest oft module
Isolated groups 1 (16 channels per group)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 1.4 W
Weight Ca. 125 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.