Parameterization

Note

The documentation for the description of configuration for version V 1.3.2 you can see in PLC configuration 3.4.5 The Setting ‘COM1 - CS31 Bus’ AC500 PLC Configuration

For version V 2.0.0 and higher see description for Control Builder Plus in chapter 2.4.3 Connecting the DC551 and S500 I/O Devices to the CS31 Bus

Module:

Nr. Name Value

Internal

value

Internal

value, type

Default Min. Max.
1 Module ID Internal

2715

*1)

Word

2715

0x0a9b

0 65535
2 Ignore module

No

Yes

0

1

Byte

No

0x00

   
14 Parameter length Internal

8

(7 * 4)

Byte

8

(7 * 4)

0 255
16 Check supply

Off

on

0

1

Byte

On

0x01

   
17 Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

Byte

8 ms

0x02

   
18 Fast counter

0

:

10 *3)

0

:

10

Byte

Mode 0

0x00

   
Nr.+1 Detection short-circuit at outputs

off

on

0

1

Byte

on

0x01

   
Nr.+1 Behaviour outputs at communication errors

Off

Last value

Substitute value

0

1

2

Byte

off

0x00

   
Nr.+1

Substitute value outputs

Bit 15 = Output 15

Bit  0 = Output  0

0…65535 0…0xffff Word 0    

*1) With CS31 and addresses less than 70, the value is increased by 1

*3) Counter operating modes Fast Counter, description of the Fast Counter Fast Counter

*4) With CS31 and addresses less than 70, without the parameter Fast counter