Diagnosis and Display¶
In case of overload or short-circuit, the outputs switch off automatically and try to switch on again cyclically. Therefore an acknowledgement of the outputs is not necessary. The LED error message, however, is stored.
Diagnosis:
| E1..E4 | d1 | d2 | d3 | d4 | Identifier 000..063  | 
AC500 display | <− Display in | |
|---|---|---|---|---|---|---|---|---|
| Class | Comp | Dev | Mod | Ch | Err | PS501 PLC browser | ||
Byte 6 Bit 6..7  | 
- | Byte 3 | Byte 4 | Byte 5 | Byte 6 Bit 0..5  | 
FBP diagnosis block | ||
| Class | Interface | Device | Module | Channel | Error Identifier | Error message | Remedy | |
| Module error DC532 | ||||||||
| 3 | 14 | 1..10 | 31 | 31 | 19 | Checksum error in the I/O module | Replace I/O module | |
| 11 / 12 | ADR | 1..10 | ||||||
| 3 | 14 | 1..10 | 31 | 31 | 3 | Timeout in the I/O module | Replace I/O module | |
| 11 / 12 | ADR | 1..10 | ||||||
| 3 | 14 | 1..10 | 31 | 31 | 40 | Different hard-/firmware versions in the module | Replace I/O module | |
| 11 / 12 | ADR | 1..10 | ||||||
| 3 | 14 | 1..10 | 31 | 31 | 43 | Internal error in the module | Replace I/O module | |
| 11 / 12 | ADR | 1..10 | ||||||
| 3 | 14 | 1..10 | 31 | 31 | 36 | Internal data exchange failure | Replace I/O module | |
| 11 / 12 | ADR | 1..10 | ||||||
| 3 | 14 | 1..10 | 31 | 31 | 9 | Overflow diagnosis buffer | New start | |
| 11 / 12 | ADR | 1..10 | ||||||
| 3 | 14 | 1..10 | 31 | 31 | 26 | Parameter error | Check master | |
| 11 / 12 | ADR | 1..10 | ||||||
| 3 | 14 | 1..10 | 31 | 31 | 11 | Process voltage too low | Check process voltage | |
| 11 / 12 | ADR | 1..10 | ||||||
| 4 | 14 | 1..10 | 31 | 31 | 45 | Process voltage is switched off (ON −> OFF) | Process voltage ON | |
| 11 / 12 | ADR | 1..10 | ||||||
| Channel error DC532 | ||||||||
| 4 | 14 | 1..10 | 2 | 16..31 | 47 | Short-circuit at a digital output | Check connection | |
| 11 / 12 | ADR | 1..10 | ||||||
Remarks:
In AC500 the following interface identifier applies: 14 = I/O-Bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2. The FBP diagnosis block does not contain this identifier.  | 
|
With “Device” the following allocation applies: 31 = Module itself, 1..10 = Expansion module 1..10, ADR = Hardware address (e.g. of the DC551)  | 
|
With “Module” the following allocation applies dependent of the master: Module error: I/O-Bus or FBP: 31 = Module itself; COM1/COM2: 1..10 = Expansion 1..10 Channel error: I/O-Bus or FBP = Module type (4 = DC); COM1/COM2: 1..10 = Expansion 1..10  | 
|
| In case of module errors, with channel “31 = Module itself” is output. | 
Displays:
During the power ON procedure, the module initializes automatically. All LEDs (except the channel LEDs) are ON during this time.
Status of the LEDs Diagnosis LEDs
| LED | Status | Color | LED = OFF | LED = ON | LED flashes | 
|---|---|---|---|---|---|
Inputs 00…15  | 
digital input | yellow | Input = OFF | Input = ON (the input voltage is even displayed if the supply voltage is OFF). | – | 
Inputs/ outputs 16…31  | 
digital input/output | yellow | Input/output = OFF | Input/output = ON (the input voltage is even displayed if the supply voltage is OFF). | – | 
| UP | Process supply voltage 24 V DC via terminal | green | Process supply voltage is missing | Process supply voltage OK | – | 
| CH-ERR1 | Channel Error, error messages in groups (digital inputs/outputs combined into the groups 1, 2, 3, 4) | red | No error or process supply voltage is missing | Serious error within the corresponding group | Error on one channel of the corresponding group (e.g. short-circuit at an output) | 
| CH-ERR2 | red | ||||
| CH-ERR3 | red | ||||
| CH-ERR4 | red | ||||
| CH-ERR *) | Module Error | red | – | Internal error | – | 
| *) All of the LEDs CH-ERR1 to CH-ERR4 light up together | |||||