Technical Data¶
The System Data of AC500-eCo are valid here System Data AC500-eCo. Only additional details are therefore documented below.
| Process supply voltage UP | Value | 
|---|---|
| Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) | 
| Rated value | 24 V DC | 
| Current consumption via UP terminal | 42 mA | 
| Max. ripple | 5 % | 
| Inrush current from UP (at power up) | 0.067 A²s | 
| Protection against reversed voltage | Yes | 
| Rated protection fuse for UP | Not necessary | 
| Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module | Ca. 5 mA | 
| Electrical isolation | Yes, per gorup | 
| Isolated groups | 5 groups (2 groups for 4 input channels, 1 group for 4 pulse train output channels, 1 group for process supply voltage, 1 group for the rest of the module) | 
| Surge-voltage (max.) | 35 V DC for 0.5 s | 
| Max. power dissipation within the module | 1.2 W | 
| Weight | ca. 125 g | 
| Mounting position | Horizontal or vertical | 
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | 