Technical Data

The System Data of AC500-eCo are valid here System Data AC500-eCo. Only additional details are therefore documented below.

Process supply voltage UP Value
Connections Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V)
Rated value 24 V DC
Current consumption via UP terminal 42 mA
Max. ripple 5 %
Inrush current from UP (at power up) 0.067 A²s
Protection against reversed voltage Yes
Rated protection fuse for UP Not necessary
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module Ca. 5 mA
Electrical isolation Yes, per gorup
Isolated groups 5 groups (2 groups for 4 input channels, 1 group for 4 pulse train output channels, 1 group for process supply voltage, 1 group for the rest of the module)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 1.2 W
Weight ca. 125 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.