Technical Data¶
The System Data of AC500-eCo System Data AC500 are valid here. Only additional details are therefore documented below.
| Process supply voltage UP | ||
| Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) | |
| Rated value | 24 V DC | |
| Current consumption | 0.10 A | |
| Inrush current (at power-up) | 0.07 A²s | |
| Max. ripple | 5 % | |
| Protection against reversed voltage | Yes | |
| Rated protection fuse for UP | Not necessary | |
| Current consumption from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | Ca. 5 mA | |
| Electrical isolation | Yes, between the channels and the rest oft module | |
| Isolated groups | 1 (4 channels per group) | |
| Surge-voltage (max.) | 35 V DC for 0.5 s | |
| Max. power dissipation within the module | 2.6 W | |
| Weight | Ca. 120 g | |
| Mounting position | Horizontal or vertical | |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | |