Diagnosis and Display¶
Diagnosis:
E1..E4 | d1 | d2 | d3 | d4 | Identifier 000..063 |
AC500 display | <− Display in | |
---|---|---|---|---|---|---|---|---|
Class | Comp | Dev | Mod | Ch | Err | PS501 PLC browser | ||
Byte 6 Bit 6..7 |
- | Byte 3 | Byte 4 | Byte 5 | Byte 6 Bit 0..5 |
FBP diagnosis block | ||
Class | Interface | Device | Module | Channel | Error Identifier | Error message | Remedy | |
Module error DX522 | ||||||||
3 | 14 | 1..10 | 31 | 31 | 19 | Checksum error in the I/O module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 3 | Timeout in the I/O module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 40 | Different hard-/firmware versions in the module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 43 | Internal error in the module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 36 | Internal data exchange failure | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 9 | Overflow diagnosis buffer | New start | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 26 | Parameter error | Check master | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 11 | Process voltage too low | Check process voltage | |
11 / 12 | ADR | 1..10 | ||||||
4 | 14 | 1..10 | 31 | 31 | 45 | Process voltage is switched off (ON −> OFF) | Process voltage ON | |
11 / 12 | ADR | 1..10 |
Remarks:
In AC500 the following interface identifier applies: 14 = I/O-Bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2. The FBP diagnosis block does not contain this identifier. |
|
With “Device” the following allocation applies: 31 = Module itself, 1..10 = Expansion module 1..10, ADR = Hardware address (e.g. of the DC551) |
|
With “Module” the following allocation applies dependent of the master: Module error: I/O-Bus or FBP: 31 = Module itself; COM1/COM2: 1..10 = Expansion 1..10 Channel error: I/O-Bus or FBP = Module type (2 = DO); COM1/COM2: 1..10 = Expansion 1..10 |
|
In case of module errors, with channel “31 = Module itself” is output. |
Displays:
During the power ON procedure, the module initializes automatically. All LEDs (except the channel LEDs) are ON during this time.
Status of the LEDs (see also section Diagnosis LEDs Diagnosis LEDs in the S500 system data)
LED | Status | Color | LED = OFF | LED = ON | LED flashes |
---|---|---|---|---|---|
Inputs 00…07 |
digital input | yellow | Input = OFF | Input = ON (the input voltage is even displayed if the supply voltage is OFF). | – |
Outputs 08…15 (relays) |
digital output | yellow | Relay output = OFF | Relay output = ON | – |
UP | Process supply voltage 24 V DC via terminal | green | Process supply voltage is missing | Process supply voltage OK | – |
CH-ERR1 | Channel Error, error messages in groups (digital inputs/outputs combined into the groups 1 and 2) | red | No error or process supply voltage is missing | Serious error within the corresponding group | Error on one channel of the corresponding group |
CH-ERR2 | red | ||||
CH-ERR *) | Module Error | red | – | Internal error | – |
*) All of the LEDs CH-ERR1 to CH-ERR2 light up together |