Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Process supply voltage UP  
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
Rated value 24 V DC
max. ripple 5 %
Protection against reversed voltage yes
Rated protection fuse on UP 10 A fast
Electrical isolation yes, per module
Current consumption  
from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module ca. 2 mA
from UP at normal operation / with outputs 0.05 A + output loads
inrush current from UP (at power up) 0.010 A²s
Max. power dissipation within the module 6 W (outputs OFF)
Weight (without Terminal Unit) ca. 300 g
Mounting position

horizontal

or vertical with derating (output load reduced to 50 % at 40 °C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.