Data Point ConfigurationΒΆ
For a user friendly configuration the Data Points will be structured as described in following table:
Data Point type | Parameters Group | Parameters DP |
---|---|---|
Timestamp | IA | |
single-point information (16) | Priority | |
double-point information | Priority | |
integrated totals | Group (none -> 4), Priority | |
measured value (16) | Type (float/norm), Priority *1) | Threshold, Normalizing |
single command | ||
double command | ||
set point command | Threshold, Normalizing | Threshold, Normalizing |
*1) Priority will only be evaluated if the Data Point group will be sent. If the Data Point is connected with and receive Function Block the parameter will be ignored. It is also only necessary for an unbalanced mode. So for 5-104 variant this parameter will be hidden in the parameter mask.
All Data Point groups that are marked with (16) can be configured as multiple Data Points where all Data Points are sent in 1 telegram. It is not possible to receive multiple Data Points.