Connection of active-type analog sensors (current) with electrically \ isolated power supply to the analog inputs¶
The following figure shows the connection of active-type analog sensors (current) with electrically isolated power supply to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Connection of active-type analog sensors (current) with electrically isolated power supply to the analog inputs
The following measuring ranges can be configured PROFIBUSâ DP Bus Module CI541-DP PROFIBUSâ DP Bus Module CI541-DP:
Current | 0…20 mA | 1 channel used |
Current | 4…20 mA | 1 channel used |
The function of the LEDs is described under PROFIBUSâ DP Bus Module CI541-DP.
Unused input channels can be left open-circuited, because they are of low resistance.
To avoid error messages through unused analog input channels in measuring range 4…20 mA, these channels should be configured as “Not used”.