PROFIBUSâ DP Bus Module CI541-DP¶
- 4 analog inputs (resolution 12 bits plus sign)
- 2 analog outputs (resolution 12 bits plus sign)
- 8 digital inputs 24 V DC
- 8 digital outputs 24 V DC, 0.5 A max
- Fast Counter
- Module-wise electrically isolated
- XC version for usage in extreme ambient conditions available
PROFIBUS® DP Bus Module CI541-DP, plugged on Terminal Unit TU510
Elements of the module | |
---|---|
1 | I/O-Bus |
2 | Allocation between terminal No. and signal name |
3 | 6 yellow LEDs to display the signal statuses of the analog inputs/outputs (AI0 - AI3, AO0 - AO1) |
4 | 8 yellow LEDs to display the signal statuses of the digital inputs (DI0 - DI7) |
5 | 8 yellow LEDs to display the signal statuses of the digital outputs (DO0 - DO7) |
6 | 2 green LEDs to display the supply voltage UP and UP3 |
7 | 3 red LEDs to display errors (CH-ERR1, CH-ERR2, CH-ERR3) |
8 | 5 System LEDs: PWR/RUN STA1 DP STA2 DP S-ERR I/O-Bus |
9 | Label |
10 | 2 rotary switches for setting the PROFIBUSâ ID |
11 | 9-pole D-SUB connector to connect the PROFIBUSâ DP signals |
12 | I/O Terminal Unit (TU509 or TU510) with 30 terminals (screw-type or spring terminals) |
13 | DIN rail |
Sign for XC version |
- Intended Purpose
- Functionality
- Electrical Connection
- Possibilities of Connection
- Connection of the digital inputs
- Connection of the digital outputs
- Connection of resistance thermometers in 2-wire configuration to the \ analog inputs
- Connection of resistance thermometers in 3-wire configuration to the \ analog inputs
- Connection of active-type analog sensors (voltage) with electrically \ isolated power supply to the analog inputs
- Connection of active-type analog sensors (current) with electrically \ isolated power supply to the analog inputs
- Connection of active-type analog sensors (voltage) with no electrically \ isolated power supply to the analog inputs
- Connection of passive-type analog sensors (current) to the analog inputs
- Connection of active-type analog sensors (voltage) to differential \ analog inputs
- Use of analog inputs as digital inputs
- Connection of analog output loads (voltage)
- Connection of analog output loads (current)
- Internal Data Exchange
- Addressing
- I/O-Configuration
- Parameterization
- Diagnosis
- LED Status Display
- Measuring Ranges
- Technical Data
- Ordering Data