Diagnosis and Display¶
Diagnosis:
E1..E4 | d1 | d2 | d3 | d4 | Identifier 000..063 |
AC500 display | <− Display in | |
---|---|---|---|---|---|---|---|---|
Class | Comp | Dev | Mod | Ch | Err | PS501 PLC browser | ||
Byte 6 Bit 6..7 |
- | Byte 3 | Byte 4 | Byte 5 | Byte 6 Bit 0..5 |
FBP diagnosis block | ||
Class | Interface | Device | Module | Channel | Error identifier | Error message | Remedy | |
Module error AI523 | ||||||||
3 | 14 | 1..10 | 31 | 31 | 19 | Checksum error in the I/O module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 3 | Timeout in the I/O module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 40 | Different hard-/firmware versions in the module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 43 | Internal error in the module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 36 | Internal data exchange failure | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 9 | Overflow diagnosis buffer | New start | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 26 | Parameter error | Check master | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 11 | Process voltage too low | Check process voltage | |
11 / 12 | ADR | 1..10 | ||||||
4 | 14 | 1..10 | 31 | 31 | 45 | Process voltage is switched off (ON -> OFF) | Process voltage ON | |
11 / 12 | ADR | 1..10 |
Channel error AI523 | |||||||
---|---|---|---|---|---|---|---|
4 | 14 | 1…10 | 1 | 0…15 | 48 | Analog value overflow or broken wire at an analog input | Check input value or terminal |
11 / 12 | ADR | 1…10 | |||||
4 | 14 | 1…10 | 1 | 0…15 | 7 | Analog value underflow at an analog input | Check input value |
11 / 12 | ADR | 1…10 | |||||
4 | 14 | 1…10 | 1 | 0…15 | 47 | Short-circuit at an analog input | Check terminal |
11 / 12 | ADR | 1…10 |
Remarks:
In AC500 the following interface identifier applies: 14 = I/O-Bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2. The FBP diagnosis block does not contain this identifier. |
|
With “Device” the following allocation applies: 31 = Module itself, 1..10 = Expansion module 1..10, ADR = Hardware address (e.g. of the DC551) |
|
With “Module” the following allocation applies dependent of the master: Module error: I/O-Bus or FBP: 31 = Module itself; COM1/COM2: 1..10 = Expansion 1..10 Channel error: I/O-Bus or FBP = Module type (1 = AI); COM1/COM2: 1..10 = Expansion 1..10 |
|
In case of module errors, with channel “31 = Module itself” is output. |
Displays:
During the power ON procedure, the module initializes automatically. All LEDs (except the channel LEDs) are ON during this time.
Status of the LEDs Diagnosis LEDs
LED | Status | Color | LED = OFF | LED = ON | LED flashes |
---|---|---|---|---|---|
inputs 00…07 and 08…15 | analog input | yellow | input is OFF | input is ON (brightness depends on the value of the analog signal) | – |
UP | process voltage 24 V DC via terminal | green | process voltage is missing | process voltage OK | – |
CH-ERR2 | Channel Error, error messages in groups (analog inputs or outputs combined into the groups 2 and 4) | red | no error or process voltage is missing | serious error within the corresponding group | error on one channel of the group |
CH-ERR4 | red | ||||
CH-ERR *) | Module Error | red | – | internal error | – |
*) Both LEDs (CH-ERR2 and CH-ERR4) light up together |