Technical Data of the Module¶

Process supply voltages UP  
  Rated value 24 V DC
  Max. load for the terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse on UP 10 A fast
  Electrical isolation Ethernet interface against the rest of the module, each serial and CAN port against each other and the rest of the module
  Inrush current from UP (at power up) On request
  Current consumption via UP (normal operation) 0.15 A
  Connections

Terminals 1.0, 2.0 and 3.0 for +24 V (UP)

Terminals 1.1, 2.1 and 3.1 for 0 V (ZP)

Max. power dissipation within the module 5 W
Setting of the IO Device identifier With 2 rotary switches at the front side of the module
Diagnosis See Diagnosis PROFINETâ IO Bus Module CI506-PNIO
Operation and error displays 18 LEDs (total)
Weight (without Terminal Unit) ca. 125 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

The module is protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.