Technical DataΒΆ
The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.
Process supply voltage L+ | ||
Connections | Terminal 19 for L+ (+24 V DC) and terminal 20 for M (0 V) | |
Rated value | 24 V DC | |
Current consumption via L+ terminal | 0.1 A | |
Inrush current (at power up) | 0.05 A:sup:2s | |
Max. ripple | 5 % | |
Protection against reversed voltage | Yes | |
Protection fuse for L+ | Recommended | |
Current consumption from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | Ca. 10 mA | |
Electrical isolation | No | |
Surge-voltage (max.) | 35 V DC for 0.5 s | |
Max. power dissipation within the module | 2.7 W | |
Weight | ca. 120 g | |
Mounting position | Horizontal or vertical | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |