Input Description

../_images/425fc658e38a3a570a33139000eba54e

EN

Data_Type Default_Value Range Unit
BOOL FALSE TRUE/FALSE -

The input EN has to be driven in edge triggered mode.

The execution of the Function Block is started with a positive edge on the input EN.

In the first call it evaluates its inputs and creates a local copy of them. Afterwards it starts its internal algorithm. It may take several PLC task cycles until it is executed.

Once the execution is completed DONE and its other outputs are set. To start the Function Block again a new positive edge on the input EN has to be applied.

SLOT

Data_Type Default_Value Range Unit
BYTE 0 0 … 4 (6) -

At input SLOT, the Communication Module slot is specified which should be used by the Function Block.

The internal Communication Module always has the index 0. All external Communication Modules are serially numbered from right to left, starting with 1.

DEV_NAME

Data_Type Default_Value Range Unit
STRING - - -

Input DEV_NAME describes the PROFINET IO Device to be queried. The string has a maximum length of 240 characters, including the zero terminating char. In conjunction with the SLOT value this string selects the target IO device of this request.

Valid values are (examples for the ABB devices, the hash marks # are place holders for the address selected by the rotary switch at the front of the device):

ci506-pn-##

NODE

Data_Type Default_Value Range Unit
BYTE - 1 - 127 -

Input NODE describes the target CANOPEN slave node ID for which the NMT command is intended.

OBJ_IDX

Data_Type Default_Value Range Unit
WORD - - -

Input OBJ_IDX describes the index of the CANOPEN object in the slave dictionary (refer to the CANOPEN slave EDS file) to be read.

SUB_IDX

Data_Type Default_Value Range Unit
BYTE - - -

Input OBJ_IDX describes the sub-index of the CANOPEN object in the slave dictionary (refer to the CANOPEN slave EDS file) to be read.

DATA

Data_Type Default_Value Range Unit
DWORDPOINTER - - -

Input DATA specifies the address of the variable containing the telegrams to be transmitted. This specification is usually done via the ADR operator. The node diagnostic data have to be of the data type PNIO_CANOM_NODE_DIAG_MESSAGE_TYPE defined in the library.

DATA_LEN

Data_Type Default_Value Range Unit
WORD - - -

Input DATA_LEN describes the maximum length of the SDO data to be uploaded in bytes.