Input Description

../_images/69e797e9e389c8630a33139000eba54e

FREI

Data_Type Default_Value Range Unit
BOOL - - -

Processing of the Function Block is controlled via input FREI.

FREI = FALSE:

All Function Block outputs are set to the value “FALSE”. However, this is not valid, if a job is currently being processed, i. e. processing of a job which is currently being processed, is not affected by FREI = FALSE.

FREI = FALSE/TRUE edge:

Processing of the job is enabled. Input FREI is no longer evaluated during processing of the job.

FREI = TRUE:

The Function Block is not processed, i. e. it no longer changes its outputs. However, this is not valid, if a job is currently being processed.

SLOT

Data_Type Default_Value Range Unit
BYTE - - -

Reserved for future extensions.

COM

Data_Type Default_Value Range Unit
BYTE - - -

At input COM, the number of the serial interface of the CS31 Master (AC500 or CM574) is specified.

Valid values: 0 and 1 for COM1, 2 for COM2 (CM574-RS only)